What Size Wire for a 60, 100 or 150 Amp Subpanel? Copper and Aluminum

Wire Size Calculator (AWG for Amps and Distance)The smallest copper or aluminum wire for a load in amps, and for a 3% voltage drop.
Open calculator

A 100 amp subpanel needs 3 AWG copper or 1 AWG aluminum wire for the hot conductors, and a 60 amp subpanel needs 6 AWG copper. Those are the sizes from the 75°C column of the NEC ampacity table, which is what the terminals on most panels and breakers are rated for. A long run needs larger wire to keep the voltage drop down. The wire size calculator works out your own load and distance.

Feeder wire size by breaker

For a 240 volt single-phase feeder, at 75°C. The first column of each metal is the size for the ampacity, and the second the size needed for a 150 foot run with a 3% voltage drop:

BreakerCopper (ampacity)Copper at 150 ftAluminum (ampacity)Aluminum at 150 ft
60 A6 AWG4 AWG4 AWG2 AWG
70 A4 AWG4 AWG3 AWG2 AWG
100 A3 AWG2 AWG1 AWG1/0 AWG
125 A1 AWG1 AWG2/0 AWG2/0 AWG
150 A1/0 AWG1/0 AWG3/0 AWG3/0 AWG

The neutral and the ground

  • Four wires to a subpanel. A subpanel feeder has two hots, a neutral and a separate ground. The neutral and the ground are kept apart in the subpanel.
  • The neutral carries the unbalanced load. It can be the same size as the hots, and may be smaller when the load is mostly 240 volt, but it must meet the code minimums.
  • The equipment ground is sized by the breaker (NEC Table 250.122): 10 AWG copper for 60 amps, 8 AWG for 100 amps and 6 AWG for 125 to 200 amps, or a size larger in aluminum.

Choosing copper or aluminum

  • Aluminum costs less and weighs less, so it is common for larger feeders, but needs one or two sizes larger than copper for the same current.
  • Use terminals and lugs rated for aluminum (marked AL or AL/CU), clean the wire, apply an anti-oxidant compound and tighten to the torque on the label.
  • Only the feeder is aluminum: the branch circuits in the subpanel are usually copper.

Long runs and voltage drop

A 100 amp load 300 feet away on copper needs 2/0 AWG to keep the drop to 3%, against 3 AWG for a short run. Use the voltage drop calculator to check a longer run, and see the voltage drop chart.

Before you start

  • Check that the main panel has room for the breaker and the load. A subpanel does not create capacity: the main panel and the service must carry the total.
  • Buy the wire for a feeder in conduit as individual THHN or XHHW conductors, or as a cable listed for the use, and follow the local code on burial depth for an outbuilding.
  • Get a permit and an inspection: it is the usual requirement for a new feeder and subpanel.
  • Have a licensed electrician make the connections in the main panel.

These sizes are for the standard ampacity table and a typical installation, not for service conductors, which have their own rules. Your local code and your inspector decide.

Frequently asked questions

What size wire for a 100 amp subpanel?

3 AWG copper or 1 AWG aluminum, using the 75°C column of the NEC ampacity table (100 amps). The equipment ground is 8 AWG copper (6 AWG aluminum).

What size wire for a 60 amp subpanel?

6 AWG copper or 4 AWG aluminum for the hot wires and neutral, with a 10 AWG copper ground.

What size wire for a 150 amp subpanel?

1/0 AWG copper or 3/0 AWG aluminum at 75°C.

Do I need bigger wire for a long run to a detached garage?

Maybe: the voltage drops with distance. A 100 amp load 300 feet away on copper needs 2/0 AWG to keep the drop to 3%, instead of 3 AWG for a short run.

Can I use aluminum wire for a subpanel?

Yes, aluminum feeder wire is common and cheaper, but it is one or two sizes larger than copper, needs connectors rated for it and an anti-oxidant compound, and needs to be torqued carefully.

Breaker Size CalculatorThe circuit breaker size for a load in amps or watts, and the wire to match.
Open calculator
Voltage Drop CalculatorVoltage drop in a wire run, and the smallest wire for 3% or less.
Open calculator
Wire Size Calculator (AWG for Amps and Distance)The smallest copper or aluminum wire for a load in amps, and for a 3% voltage drop.
Open calculator

More guides

Tools & materials for this project

Affiliate links As an Amazon Associate we earn from qualifying purchases. These links do not change what you pay.

Estimates only. Quantities depend on your materials, site and supplier. Confirm important numbers before you order, and follow local building codes for anything structural.