How Many Wires Fit in Conduit? EMT and PVC Fill Chart
Part of the project planner: Sizing a circuit: watts, amps, wire and breaker.
A 3/4 inch EMT holds up to 16 wires of 12 AWG THHN, and a 1/2 inch EMT holds 9. The limit comes from the National Electrical Code, which lets the wires fill only 40% of the inside of the conduit when there are three or more of them. The conduit fill calculator works out the fill for your own mix of conduit and wire, including a ground wire of another size.
Wires allowed in EMT
Most THHN or THWN-2 wires of one size, by trade size. The ground wire counts as one of them.
| Wire | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in |
|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 26 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 |
Wires allowed in PVC Schedule 40
PVC Schedule 40 has a thicker wall than EMT, so it holds slightly fewer wires of the same trade size.
| Wire | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in |
|---|---|---|---|---|---|---|
| 14 AWG | 11 | 21 | 34 | 60 | 82 | 135 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 |
| 8 AWG | 3 | 5 | 9 | 16 | 21 | 36 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 26 |
| 4 AWG | 1 | 2 | 4 | 7 | 9 | 16 |
Bigger conduit
EMT, for the larger sizes used for feeders:
| Wire | 2-1/2 in | 3 in | 3-1/2 in | 4 in |
|---|---|---|---|---|
| 12 AWG | 176 | 266 | 347 | 443 |
| 10 AWG | 111 | 167 | 219 | 279 |
| 8 AWG | 64 | 96 | 126 | 161 |
| 6 AWG | 46 | 69 | 91 | 116 |
| 4 AWG | 28 | 43 | 56 | 71 |
Which conduit for a common job?
The smallest conduit for the wires in a common job, counting the ground:
| Job | Wires | Smallest EMT | Smallest PVC |
|---|---|---|---|
| One 20 A circuit (hot, neutral and ground, 12 AWG) | 3 | 1/2 in | 1/2 in |
| Two 20 A circuits (2 hots, 2 neutrals, ground, 12 AWG) | 5 | 1/2 in | 1/2 in |
| Three 15 A circuits (3 hots, 3 neutrals, ground, 14 AWG) | 7 | 1/2 in | 1/2 in |
| 60 A subpanel feeder (2 hots and a neutral in 6 AWG, 10 AWG ground) | 4 | 3/4 in | 3/4 in |
| 100 A subpanel feeder (2 hots and a neutral in 3 AWG, 8 AWG ground) | 4 | 1 in | 1 in |
These are the sizes for fill only. Check the wire gauge for the load with the wire size calculator first.
The rules behind the chart
- 40% for three or more wires, 31% for two, 53% for one. These are the limits in NEC Chapter 9, Table 1. The wires need room so that they can be pulled and so that the heat can get away.
- The area of the wire includes its insulation. A 12 AWG THHN wire takes 0.0133 square inches. The conduit areas are in Table 4 and the wire areas in Table 5.
- Same-size wires round up. When every wire is the same size, a result of 0.8 or more above a whole number may be rounded up. That is why 3/4 inch EMT holds 6 wires of 8 AWG even though 5.8 would fit by area.
- Mixed sizes add up by area. Three 12 AWG wires and a 10 AWG ground add up to 0.0610 square inches, which is 20.1% of a 1/2 inch EMT, and there is room for 7 such wires.
- Short nipples may be fuller. A conduit nipple of 24 inches or less may be filled to 60%.
- Only the wire types in the table. The areas are for THHN, THHW and THWN-2. Other insulation types such as XHHW are thicker. Romex (NM-B) cable is a different product and is not counted this way.
Fill is not the only limit
- Heat. More than three current-carrying wires in a conduit lower the ampacity of every wire (NEC 310.15). Four to six current-carrying wires are derated to 80%, and seven to nine to 70%. A conduit that is physically large enough may still need larger wire.
- Pulling. A long run or several bends make a full conduit hard to pull. Stay near 30% fill if you can, and use wire lubricant.
- Bends. No more than 360 degrees of bends (four 90 degree bends) are allowed between pull points. Put a pull box in a long run.
- Future circuits. A size up costs little. Adding a circuit to a full conduit means pulling everything again.
Worked example
You want to pull nine wires of 12 AWG THHN (no separate ground) in a 1/2 inch EMT. The wires cover 0.1197 square inches of the conduit, which is 39.4% and just under the 40% limit, so that is the most the conduit will take. A tenth wire does not fit, and you would need 3/4 inch EMT. Our own run of six wires and a ground in 3/4 inch EMT is 17.5% full.
Estimates only: the NEC and your local code are the rule, and your inspector decides. Have an electrician look at any work on the service or the panel.
Frequently asked questions
How many 12 gauge wires fit in 1/2 inch conduit?
9 wires of 12 AWG THHN fit in 1/2 inch EMT and 8 in 1/2 inch PVC Schedule 40. The ground wire counts as one of them.
How many wires fit in 3/4 inch conduit?
16 wires of 12 AWG, 10 of 10 AWG or 22 of 14 AWG in EMT. In 3/4 inch PVC Schedule 40 it is 15, 9 and 21.
What is the 40 percent rule for conduit fill?
Three or more wires may fill no more than 40% of the inside area of the conduit. The limit is 53% for a single wire and 31% for two wires.
Does the ground wire count?
Yes. Every wire in the conduit counts, including the ground and the neutral. Six 12 AWG wires and a 12 AWG ground in 3/4 inch EMT are 17.5% full.
Do I count a bare ground wire?
Yes: a bare equipment grounding conductor counts toward the fill, using its own area from the NEC table.