How Thick Should Insulation Be? Thickness for a Target U-Value
The thickness of insulation for a target U-value comes from the resistance you have to add. To go from U 2.0 to 0.16 you must add 5.75 m²K/W, which is 127 mm of PIR board with a λ of 0.022. The insulation thickness calculator does it for your case.
Thickness for each target
In mm, before thermal bridging, from a U-value of 2.0 (a solid wall) or 0.5, with PIR (λ 0.022), and from 2.0 with mineral wool (λ 0.044):
| Target U-value | PIR from 2.0 | PIR from 0.5 | Mineral wool from 2.0 |
|---|---|---|---|
| 0.3 | 62 mm | 29 mm | 125 mm |
| 0.25 | 77 mm | 44 mm | 154 mm |
| 0.18 | 111 mm | 78 mm | 222 mm |
| 0.16 | 127 mm | 94 mm | 253 mm |
| 0.15 | 136 mm | 103 mm | 271 mm |
Thickness for each insulation, from U 2.0 to 0.16
| Insulation | λ (W/mK) | Thickness |
|---|---|---|
| Phenolic board | 0.018 | 104 mm |
| PIR board | 0.022 | 127 mm |
| Mineral wool loft roll | 0.044 | 253 mm |
The λ is the figure on the product, and brands differ, so check it. A better insulation (a lower λ) needs less thickness for the same result.
The targets in Approved Document L (England)
- New home: roof 0.16, wall 0.26, floor 0.18.
- New element on an existing home: roof 0.15, wall 0.18, floor 0.18.
- Existing element that is upgraded: roof 0.16, wall with internal or external insulation 0.30, cavity wall 0.55, floor 0.25.
Things to remember
- The calculation is for a continuous layer. Studs and joists add thermal bridging, so allow more thickness.
- Use the U-value of the wall you have from a survey or an EPC, since a guess makes the answer wrong.
- Wales and Scotland have different targets from England.
- Insulating inside a solid wall can cause damp if it is done badly: follow the system maker.
See also the loft insulation calculator and the heat pump calculator. These are estimates: confirm the details with a designer or building control.
Frequently asked questions
How thick should insulation be?
It depends on the starting U-value, the target and the insulation: 127 mm of PIR board (λ 0.022) takes a U-value of 2.0 to 0.16, before thermal bridging.
How do you work out the thickness from the U-value?
Take 1 divided by the target U-value, less 1 divided by the U-value now. That is the resistance to add. Multiply it by the λ of the insulation, in W/mK, to get the thickness in metres.
What are the U-value targets in England?
Approved Document L gives 0.16 for the roof, 0.26 for the wall and 0.18 for the floor of a new home. For a retained roof that is upgraded it is 0.16, for a wall with internal or external insulation 0.30 and for a floor 0.25.
Does this work for Scotland and Wales?
No: the targets are for England. Scotland and Wales have their own rules, so check them.
Why is the real thickness more?