Extract Fan Rate Calculator (UK): What l/s Do the Building Regulations Need?

Pick the room and the type of fan. You get the lowest extract rate Approved Document F allows, in litres per second and cubic metres per hour, and the whole-dwelling ventilation rate for your home.

UK edition. Switch to the US edition for feet, inches and US gallons.

Jump to your result ↓

Your project

Results

Example job shown. Change the numbers to match yours.

Least extract rate for this room
15 l/s
Intermittent extract (Table 1.1)
Same rate in cubic metres per hourMany fans are rated this way: 1 l/s = 3.6 m³/h
54.0 m³/h
Same rate in cubic feet per minute
31.8 CFM

Whole-dwelling ventilation

Least rate by number of bedroomsTable 1.3: 19 l/s for one bedroom, plus 6 for each extra
31 l/s
Least rate by floor area (0.3 l/s per m²)
27.0 l/s
Whole-dwelling rate to meet (the higher)112 m³/h
31.0 l/s
  • These are the minimum rates in Approved Document F Volume 1 (2021 edition, dwellings). A fan must achieve its rate in the installed system, so allow for the duct length and bends: the rating on the box is measured with no duct. Fans should be fitted as high as practical in the room and no more than 400 mm below the ceiling. For a kitchen the cooker hood must extract outside to use the 30 l/s rate, and it should span the full width of the hob. Intermittent fans give the room its rate when they run, and the home still needs background or whole-house ventilation. A competent installer should size and commission the system, and electrical work in a bathroom must meet the wiring regulations (Part P).

Before you buy: round up to whole packs, check the size printed on the label, and add a little spare. Your supplier has the final say.

How this calculator works

Approved Document F gives the least rate an extract fan must achieve in each wet room. An intermittent fan (switched on, or on a humidity sensor) needs 15 l/s in a bathroom, 30 l/s in a utility room, 6 l/s in a separate WC and 30 l/s in a kitchen where the cooker hood extracts to the outside, or 60 l/s if it does not. Fans that run all the time have lower boost rates: 13 l/s in a kitchen, 8 in a utility room and bathroom, and 6 in a WC.

m³/h = l/s × 3.6 whole-dwelling rate = the higher of 0.3 l/s × floor area (m²) and 13 + 6 per bedroom

Worked example: a bathroom fan needs 15 l/s, which is 54 m³/h. A kitchen fan needs 30 l/s (108 m³/h) with a hood that extracts outside, and 60 l/s (216 m³/h) without. A 3-bedroom, 90 m² home needs a whole-dwelling rate of 31 l/s (the bedroom figure beats 0.3 × 90 = 27); a 4-bedroom, 140 m² home needs 42 l/s.

Assumptions and sources
  • These are the minimum rates in Approved Document F Volume 1 (2021 edition, dwellings). A fan must achieve its rate in the installed system, so allow for the duct length and bends: the rating on the box is measured with no duct. Fans should be fitted as high as practical in the room and no more than 400 mm below the ceiling. For a kitchen the cooker hood must extract outside to use the 30 l/s rate, and it should span the full width of the hob. Intermittent fans give the room its rate when they run, and the home still needs background or whole-house ventilation. A competent installer should size and commission the system, and electrical work in a bathroom must meet the wiring regulations (Part P).

The formula and a worked example are shown above, so you can check any result by hand. Read how we calculate and check our numbers. Results are estimates for planning: supplier products vary, so check the size printed on the label.

Minimum extract rates, Approved Document F

Intermittent extract rates (Table 1.1) with the equivalent in m³/h.

Rooml/sm³/h
Kitchen (hood extracting outside)30108.0
Kitchen (no hood or recirculating)60216.0
Utility room30108.0
Bathroom1554.0
Sanitary accommodation (WC)621.6

Tips before you buy

  • The 30 l/s kitchen rate needs a hood that extracts outside, wide enough for the whole hob. A recirculating hood does not count, so you would need 60 l/s from a fan in the wall or ceiling.
  • Fans are marked in l/s or m³/h. To convert, multiply litres per second by 3.6. Check the rate quoted is for the installed fan with its ducting, not the free-air figure.
  • Long or narrow ducts and sharp bends cut the airflow. Use the shortest, straightest duct, in smooth rigid pipe, and insulate it where it runs through a cold loft to stop condensation running back.
  • In a bathroom with a shower, a humidity-sensing fan with overrun is sensible. Bathroom fans have electrical zone rules: check the IP rating.
  • A very airtight home needs a planned whole-house system, with background ventilators or mechanical supply to replace the air the fans take out.

Tools & materials for this project

Affiliate links As an Amazon Associate we earn from qualifying purchases. These links do not change what you pay.

Frequently asked questions

What extract fan rate does a bathroom need in the UK?

15 l/s (54 m³/h) for an intermittent fan, from Table 1.1 of Approved Document F. A continuous fan needs a high rate of 8 l/s.

How many l/s for a kitchen extractor fan?

30 l/s if the cooker hood extracts outside, and 60 l/s if there is no hood or it recirculates.

How do I convert l/s to m³/h?

Multiply by 3.6. 15 l/s is 54 m³/h and 30 l/s is 108 m³/h.

What is the minimum extract rate for a toilet?

6 l/s (21.6 m³/h) for a separate WC, or use purge ventilation such as an openable window.

What is the whole-dwelling ventilation rate?

The higher of 0.3 l/s per m² of floor area and the bedroom figure in Table 1.3 (19 l/s for one bedroom, plus 6 for each extra). A 3-bedroom, 90 m² home needs 31 l/s.

Add this calculator to your website

Running a blog, a contractor site or a class page? You can put this calculator on it for free. Copy the code below, and please leave the link underneath the calculator in place. The small script just resizes the frame to fit the results; if your site strips scripts, the calculator still works inside a scrolling frame.