What Size Boiler for a 50 m² House?

A 50 m² home with average insulation loses about 3.5 kW on a cold day. A combi boiler for one 10 litre a minute shower should be 24 kW, because the hot water needs 20.9 kW, while a system boiler with a cylinder can be 12 kW.

Jump to your result ↓

Your project

Results

Example job shown. Change the numbers to match yours.

Boiler output to look for
24 kW
The next standard size above 20.9 kW
Heat the home needs on a cold day70 W per m² of floor
3.5 kW
Power to heat the hot water1 outlet at 10 litres a minute, heated by 30°C
20.9 kW
Load the boiler must meetThe larger of the heating and the hot water
20.9 kW
  • A combi boiler heats the hot water directly, so its output is set mostly by the hot water you want at once, which is why a 24 to 30 kW combi suits a house that needs only 7 kW for heating: a modern boiler turns down (modulates) to run at a low output for the radiators. A system or regular boiler stores hot water in a cylinder, so it is sized for the heating. This is a rule-of-thumb estimate: ask a Gas Safe registered engineer for a room-by-room heat loss calculation, and size radiators with the radiator size calculator.

Before you buy: round up to whole packs, check the size printed on the label, and add a little spare. Your supplier has the final say.

Boiler size for a 50 m² home, by insulation

A 50 m² home is a one-bedroom flat or a small terraced cottage. The heating load is the heat the home loses on a cold day. A system or regular boiler is sized on the heating with 10% for reheating the cylinder. The yearly gas cost assumes an 88% efficient boiler and 6.3p per kWh of gas, and the heat pump size is the next common model above the load.

InsulationHeating loadSystem boilerGas for heating a yearHeat pump size
Poor (solid walls, single glazing)5.0 kW12 kW£6445 kW
Average (cavity walls, double glazing)3.5 kW12 kW£4305 kW
Good (well insulated)2.5 kW12 kW£2865 kW
Excellent (new build)1.5 kW12 kW£1795 kW

Combi boiler size by hot water use

A combi heats water as it flows, so its size comes from the hot water you draw at once, heated by 30°C. The load is the larger of the hot water and the 3.5 kW heating load.

Hot water at onceLoadCombi size
One shower, 8 litres a minute16.7 kW24 kW
One shower, 10 litres a minute20.9 kW24 kW
One shower, 12 litres a minute25.1 kW28 kW
Two showers at once, 10 litres a minute41.8 kW42 kW
Two showers at once, 12 litres a minute50.2 kWask an engineer

What sets the size

For a 50 m² home the heating load is smaller than the power a combi needs for one shower (20.9 kW), even with poor insulation, so the hot water sets the size of a combi. A modern boiler turns down (modulates) to run the radiators at a fraction of its rating.

These are rule-of-thumb figures, not a heat loss survey. Ask a Gas Safe registered engineer for a room-by-room heat loss calculation and quote, and size each room with the radiator size calculator. The boiler size guide explains combi and system boilers.

Want to change anything else? The calculator above is the full Boiler Size Calculator (UK): What kW Boiler Do I Need?: edit any number and the results update instantly.

Tools & materials for this project

Affiliate links As an Amazon Associate we earn from qualifying purchases. These links do not change what you pay.

Frequently asked questions

What size boiler do I need for a 50 m² house?

A 50 m² home with average insulation loses about 3.5 kW on a cold day. A combi boiler supplying one 10 litre a minute shower should be 24 kW, because the hot water needs more power than the heating. A system or regular boiler with a cylinder can be 12 kW.

Is a 24 kW combi big enough for a 50 m² house?

Yes for one shower at a time: a 50 m² home needs 3.5 kW of heating and one 10 litre a minute shower needs 20.9 kW. Two showers at once need 41.8 kW, which is a 42 kW combi, or a system boiler with a cylinder.

What size heat pump for a 50 m² house?

About 5 kW for average insulation, from a heat loss of 3.5 kW. Over a year the heating uses about 6,000 kWh of heat, costing about £430 with gas or £520 with a heat pump at a SCOP of 3, at 6.3p gas and 26p electricity.

Related sizes and guides