What Size Heater for a 12 × 20 ft Garage?

A 12 × 20 ft garage with insulated walls and ceiling needs about 6,936 BTU (2,033 W) to hold 50°F when it is 20°F outside, so a 3,000 W electric heater drawing 12.5 amps at 240 V. With no insulation it needs 14,634 BTU.

Jump to your result ↓

Your project

°F
°F

50°F stops things freezing and is comfortable in a coat. 60°F or more suits working for long periods.

$

Results

Example job shown. Change the numbers to match yours.

Heater size to buy
6,936 BTU per hour
Heat loss plus a 25% margin
In watts (electric)
2,033 W
Next standard electric size
3,000 W
Current at 240 VThe circuit breaker needs to be rated at 125% of this
12.5 A
Running cost, if it runs non-stop
0.35 dollars per hour
Heat the garage loses to hold the temperature
5,549 BTU per hour
Temperature rise
30 °F
  • This is the heat needed to hold the temperature in steady conditions. A large amount of concrete, tools and vehicles will take hours to warm, and opening the door loses a lot of heat. For a quick warm-up, choose the next size up. A fuel-burning heater needs a vent or a heater rated for garages, and a garage with a car or fuel in it has special safety rules: follow the heater's manual and your local code.

Before you buy: round up to whole packs, check the size printed on the label, and add a little spare. Your supplier has the final say.

Heater size for a 12 × 20 ft garage, by insulation

An 8 ft ceiling, holding 50°F when it is 20°F outside, with a 25% margin. Amps are at 240 V for the standard electric size.

InsulationBTU per hourWattsElectric sizeAmps
None: bare studs, plain door14,634 BTU4,289 W5,000 W20.8 A
Walls and ceiling insulated6,936 BTU2,033 W3,000 W12.5 A
Well insulated, door too3,598 BTU1,054 W1,500 W6.3 A

How cold it gets where you live

The same garage with insulated walls and ceiling, held at 50°F, for different design temperatures outside:

Coldest outdoor temperatureHeat neededElectric size
0°F11,560 BTU4,000 W
10°F9,248 BTU3,000 W
20°F6,936 BTU3,000 W
30°F4,624 BTU1,500 W

How warm you want it

At 20°F outside, insulated. The last column is the cost per hour at 17¢ a kWh if the heater runs non-stop at the heat-loss rate:

Temperature insideHeat neededElectric sizeCost per hour
40°F4,624 BTU1,500 W$0.23
50°F6,936 BTU3,000 W$0.35
60°F9,248 BTU3,000 W$0.46
70°F11,560 BTU4,000 W$0.58

A 12 × 20 ft garage: one car, or a workshop

A 12 × 20 ft space is a small one-car garage or a typical workshop bay. With the walls and ceiling insulated it needs about 6,936 BTU, so a 3,000 W heater. A 1,500 W plug-in space heater gives 5,118 BTU, which is enough here only if the space is well insulated, including the door.

For a bench you use for an hour at a time, a radiant (infrared) heater aimed at where you stand usually warms you faster than heating all the air.

Enter your own garage in the garage heater size calculator, or read what size heater for a garage for breakers, fuel and safety.

Want to change anything else? The calculator above is the full Garage Heater Size Calculator: edit any number and the results update instantly.

Tools & materials for this project

Affiliate links As an Amazon Associate we earn from qualifying purchases. These links do not change what you pay.

Frequently asked questions

What size heater for a 12 × 20 ft garage?

About 6,936 BTU, or 2,033 W, to hold 50°F when it is 20°F outside, with insulated walls and ceiling and an 8 ft ceiling. That is a 3,000 W electric heater. With no insulation it needs 14,634 BTU.

How many amps does a heater for a 12 × 20 garage draw?

A 3,000 W heater draws 12.5 amps at 240 V. The breaker must be rated for 125% of that, and the wire sized to the breaker.

How much does it cost to heat a 12 × 20 ft garage?

About $0.35 an hour at 17¢ a kWh if the heater ran non-stop at the heat-loss rate. In practice the thermostat cycles it, and a garage you heat only while you work costs far less.

Will a 1,500 W space heater heat a 12 × 20 garage?

A 1,500 W heater gives 5,118 BTU an hour. That is enough only if the garage is well insulated, including the door (3,598 BTU).

Related sizes and guides

Related sizes

Estimates only. Results assume standard materials and simple shapes. Supplier products vary, and the final call on quantity, structure and safety is yours. Check your local code and your supplier's guidance before ordering.