Heater size for a 22 × 22 ft garage, by insulation
An 8 ft ceiling, holding 50°F when it is 20°F outside, with a 25% margin. Amps are at 240 V for the standard electric size.
| Insulation | BTU per hour | Watts | Electric size | Amps |
|---|---|---|---|---|
| None: bare studs, plain door | 23,968 BTU | 7,025 W | 7,500 W | 31.3 A |
| Walls and ceiling insulated | 11,524 BTU | 3,377 W | 4,000 W | 16.7 A |
| Well insulated, door too | 6,023 BTU | 1,765 W | 3,000 W | 12.5 A |
How cold it gets where you live
The same garage with insulated walls and ceiling, held at 50°F, for different design temperatures outside:
| Coldest outdoor temperature | Heat needed | Electric size |
|---|---|---|
| 0°F | 19,206 BTU | 7,500 W |
| 10°F | 15,365 BTU | 5,000 W |
| 20°F | 11,524 BTU | 4,000 W |
| 30°F | 7,682 BTU | 3,000 W |
How warm you want it
At 20°F outside, insulated. The last column is the cost per hour at 17¢ a kWh if the heater runs non-stop at the heat-loss rate:
| Temperature inside | Heat needed | Electric size | Cost per hour |
|---|---|---|---|
| 40°F | 7,682 BTU | 3,000 W | $0.38 |
| 50°F | 11,524 BTU | 4,000 W | $0.57 |
| 60°F | 15,365 BTU | 5,000 W | $0.77 |
| 70°F | 19,206 BTU | 7,500 W | $0.96 |
A 22 × 22 ft garage: two cars with room to walk
At 22 × 22 ft there is space to open the car doors and keep a bench. Insulated, it needs 11,524 BTU, or 3,377 W, so the next standard size is 4,000 W at 16.7 amps on 240 V.
If you only need it above freezing, to protect paint, water lines and batteries, set it to 40°F: that needs 3,000 W.
Enter your own garage in the garage heater size calculator, or read what size heater for a garage for breakers, fuel and safety.
Want to change anything else? The calculator above is the full Garage Heater Size Calculator: edit any number and the results update instantly.
Tools & materials for this project
Affiliate links As an Amazon Associate we earn from qualifying purchases. These links do not change what you pay.
Frequently asked questions
What size heater for a 22 × 22 ft garage?
About 11,524 BTU, or 3,377 W, to hold 50°F when it is 20°F outside, with insulated walls and ceiling and an 8 ft ceiling. That is a 4,000 W electric heater. With no insulation it needs 23,968 BTU.
How many amps does a heater for a 22 × 22 garage draw?
A 4,000 W heater draws 16.7 amps at 240 V. The breaker must be rated for 125% of that, and the wire sized to the breaker.
How much does it cost to heat a 22 × 22 ft garage?
About $0.57 an hour at 17¢ a kWh if the heater ran non-stop at the heat-loss rate. In practice the thermostat cycles it, and a garage you heat only while you work costs far less.
Will a 1,500 W space heater heat a 22 × 22 garage?
A 1,500 W heater gives 5,118 BTU an hour. That is not enough even when the garage is well insulated (6,023 BTU). It will take the chill off a small area near you.